Baxi Solo 2 PF Quick Start Manual Page 9

  • Download
  • Add to my manuals
  • Print
  • Page
    / 44
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 8
3.0 System Details
9
3.6 Sealed Systems (Fig. 8)
1. SAFETY VALVE - A safety valve complying
with the requirements of BS 6750 Part 1 must be
fitted close to the boiler on the flow pipe by means
of a horizontal or vertically upward connection
with no intervening valve or restrictions and
should be positioned to facilitate testing. The
valve should be pre-set and non-adjustable to
operate at a pressure of 3 bar (45 Ibf/in
2
). It must
be arranged to discharge any water or steam
through a pipe to a safe outlet position.
2. PRESSURE GAUGE - A pressure gauge of
minimum range 0-4 bar (0-60 Ibf/in
2
) with a fill
pressure indicator must be fitted to the system,
preferably at the same point as the expansion
vessel in an easily visible position.
3. EXPANSION VESSEL - An expansion vessel
complying with the requirements of BS 4814 must
be fitted to the system by means of a connection
close to the inlet side of the circulating pump in
accordance with the manufacturers instructions,
the connecting pipe being unrestricted and not
less than 15mm (
1
/
2
in) nominal size. The volume
of the vessel should be suitable for the system
water content and the nitrogen or air charge
pressure should not be less than the system static
head (See Table. 1).
Further details of sealed system design can be
obtained from BS 5449 and the British Gas
publication entitled 'Specifications for Domestic
Wet Central Heating Systems'.
4. FILLING POINT - A filling point and an
approved stop valve to BS 1010 must be fitted at
low level and the method used for filling the
system should be approved by the local water
undertaking. For further details see BS 6798.
5. MAKE UP SYSTEM - A method of replacing
water lost from the system should be provided
either by means of a make up vessel of not more
than 3 litres (5 pints) capacity, mounted above the
highest point of the system, or by pre-
pressurisation of the system.
6. VENTING - A method of venting the system
during filling and commissioning must be provided
by fitting automatic air vents or by venting
manually.
7. HOT WATER STORAGE - The hot water
storage vessel must be of the indirect coil type. All
components used in the system must be suitable
for operation at 110°C (230°F) and at the
pressure allowed by the safety valve.
Initial System
Pressure (Bar)
Vessel Charge
Pressure (Bar)
Multiply Total
Water Content Of
System By (Litres)
0.067
0.112
0.207
0.441
0.087
0.152
0.330
0.125
0.265
0.5
1.0
1.5
2.0
1.0
1.5
2.0
1.5
2.0
0.5
1.0
1.5
Example :-
Then :-
System Volume = 75 litres
Vessel Charge Pressure = 1.0 bar
Initial System Pressure = 1.5 bar
75 x 0.152 = 11.4 litres
Expansion Vessel Volume
Method of determining minimum
value of expansion vessel volume for
sealed systems using Baxi Boilers
NOTE
Where a vessel of the calculated size is not obtainable
then the next available larger size should be used.
Safety
Valve
Pressure
Gauge
Pump
Filling
Point
Air
Vent
3 Litre
Top Up Bottle
(if required)
Radiator
Circuit
Expansion
Vessel
System Drains
at Low Point
Max Boiler Flow
Temp = 82° C
Boiler
Fig. 8
Table. 1
Page view 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 ... 43 44

Comments to this Manuals

No comments