3.0 System Details
8
3.3 Pipework
1. The sizes of flow and return pipes from the
boiler should be determined by normal methods,
according to the requirements of the system.
2. An 11 °C (20°F) drop in temperature across the
system is recommended.
3.4 System Controls
1. For optimum operating conditions, the heating
system into which the boiler is installed should
include a control system.
2. Such a system will comprise of a timer control
and separate room or cylinder thermostats as
appropriate.
3. The boiler should be controlled so that it
operates on demand only.
4. Operation of the system under control of the
boiler thermostat only does not produce the best
results.
5. A frost thermostat is fitted integrally to the
appliance controls and will protect the boiler from
frost damage by operating the burner when the
water temperature in the boiler drops towards
freezing point. The boiler will fire as necessary to
maintain a temperature above freezing.
NOTE: The frost thermostat operates even if
the boiler thermostat is in the OFF ('0') position
and it is necessary therefore, if the system is
drained, for the external electrical and gas
supplies to be isolated. It is recommended that
a label be affixed to the appliance to draw
attention to the fact that the system has been
drained.
3.5 Low Head Installation
For boilers up to 50,000 Btu/h output
1. Using a close couple arrangement the minimum
head is as shown in the diagrams (Figs. 5 & 6)
subject to the following conditions:
a) The correct heat input.
b) The pump being adjusted to give an 11
o
C
drop across the boiler.
c) The pump must be fitted on the flow.
d) The pump must be fitted in accordance with
the pump manufacturer's instructions.
e) The open vent pipe must be taken up from a
tee in a horizontal section of the flow pipe.
Alternative Low Head Installation for all Solo 2 PF
(Fig. 7)
2. If less height is available then a combined vent
and feed pipe may be connected. This must be a
minimum of 22mm diameter. It is recommended
that an air separator is fitted when using a
combined feed and vent pipe.
Typical Low Head Installation
If Conditions Require,
This System Possible
Alternative Low Head Installation
Boiler
500mm
45°
22mm
Open Vent
1000mm
Min
150mm
Max
15mm
Cold
Feed
400mm
Min Head
Return
Pump
Flow
Boiler
500mm
45°
22mm
Open Vent
400mm
Min Head
1000mm
Min
Automatic
Air Vent
15mm
Cold
Feed
150mm
Max
Return
Pump
Flow
Return
Pump
Flow
Boiler
200mm
Min
Air
Separator
22mm
Feed & Vent
Pipe
Fig. 5
Fig. 6
Fig. 7
Page view 7