28 EcoBlue Plus Combi 7212136 - 02 (08/14)
5 Before Installation
5.3 Choice of the Location
5.3.1 Location of the Appliance
1. The boiler may be fitted to any suitable wall with the flue
passing through an outside wall or roof and discharging to
atmosphere in a position permitting satisfactory removal of
combustion products and providing an adequate air supply. The
boiler should be fitted within the building unless otherwise
protected by a suitable enclosure i.e. garage or outhouse. (The
boiler may be fitted inside a cupboard-see Section 5.3.4).
2. Where the boiler is sited in an unheated enclosure and during
periods when the heating system is to be unused it is
recommended that the permanent live is left on to give BOILER
frost protection. NOTE: THIS WILL NOT PROTECT THE
SYSTEM !
3. If the boiler is fitted in a room containing a bath or shower
reference must be made to the relevant requirements.
In GB this is the current I.E.E. Wiring Regulations and Building
Regulations.
In IE reference should be made to the current edition of I.S. 813
“Domestic Gas Installations” and the current ETCI rules.
4. If the boiler is to be fitted into a building of timber frame
construction then reference must be made to the current edition
of Institute of Gas Engineers Publication IGE/UP/7 (Gas
Installations in Timber Framed Housing).
5.3.2 Data Plate
1. The boiler data badge gives details of the model, serial
number and Gas Council number and is situated on the boiler
lower panel. It is visible when the control box is lowered (Fig. 6).
5.3.3 Bath & Shower Rooms
Where an integral timer is NOT FITTED the boiler has a
protection rating of IPX5D and if installed in a room
containing a bath or shower can be within Zone 2 (but
not 0 or 1).
Figs. A & B shows zone dimensions for a bathtub. For other
examples refer to the Current I.E.E. Wiring Regulations).
Reference must be made to the relevant requirements.
In GB this is the current I.E.E. Wiring Regulations and Building
Regulations. In IE reference should be made to the current
edition of I.S. 813 “Domestic Gas Installations” and the current
ETCI rules.
If the boiler is fitted with an integral timer it CANNOT be
installed in Zone 0, 1 or 2.
5.3.4 Ventilation
1. Where the appliance is installed in a cupboard or
compartment, no air vents are required. BS 5440: Part 2 refers
to room sealed appliances installed in compartments. The
appliance will run sufficiently cool without ventilation.
Zone 2
Zone 1
Zone 0
Zone 2
Zone 2
Window
Recess
Window
Recess
0.6 m
Ceiling
Outside Zones
Zone 2
Zone 1
Zone 0
2.25 m
Window Recess
Zone 2
0.6 m
Fig. A
Fig. B
In GB Only
In GB Only
Fig. 6
Data Badge