7215845 - 01 (08/14) MainEco Heat 57
Troubleshooting 11
Remedial actions by service
engineer
Status
signal
Description Possible cause s
1 flash
red
Sensor error
•Bad connection to flow or
return temperature sensor
•Fault with flow or return
temperature sensor(s)
•Low or no flow through boiler
Reverse flow through boiler
•Check connections to
temperature sensors/PCB and
condition of wiring loom
•Check resistance
of
temperature sensors
•Check pump operation and
system circulation
2 flashes
red
High
temperature
protection
Over-temperature thermostat on
heat exchanger activated
•No water flow through heat
exchanger
Over-temperature thermostat
fault or bad connection (open
circuit).
•PCB over-temperature condition
•Flue fault resulting in
recirculation or activation of air
pressure switch (if fitted)
•Check connections to and
operation of O/T thermostat
and air pressure switch (if
fitted) and PCB and condition
of wiring loom
•Check system pressure or that
system is not air- locked
•Check pump operation and
system circulation
•Check flue co ndition
3 flashes
red
Ignition fault
•No ignition
•No flame detected following
ignition
•False flame signal detected
Repeated loss of flame detected
•Check earthing of the appliance
•Check ignition electrode
condition and clean/replace if
necessary
•Check gas valve operation
•Check flue condition
•Check correct
combustion/gas
valve settings
4 flashes
red
Fan fault
•Fan calibration error
•Fan failure
If fan operates, check flue
installation and condition.
•Replace control/fan assy
5 flashes
red
Parameter fault
•Bad connection to PU
Parameter error or faulty PU
PCB and condition of wiring
loom
•Replace PU and recommission
6 flashes
red
Miscellaneous
•Bad connection or wiring fault
internal or external to the boiler
Parameter error
Communication error
•Check all wiring connections
are
correctly made
Using a service tool or Recom
software chec k all parameter
settings
If necessary replace PU
and/or control/fan assy
•Check condensate drain for
blockage
Lock-out conditions (Red flashes on “chimney sweep”)
The following TABLE describes the conditions that may result in
a lock-out condition and red flashing signal being displayed.
To reset a lock-out condition press and hold the reset button
until the fault indication flashes rapidly and goes out.
NOTE: a lock-out condition can be re-set up to 5 times within
one hour using the reset button. Any repeating fault should be
fully investigated and appropriate remedial actions taken by a
Gas Safe registered service engineer.