ECOSKID 21
Balanced Horizontal Flue
Wall Plate
1000mm extension piece
complete with clamp and
wall support bracket.
P
art No = 5136148
Part No = 5136159
Condensate drain with trap,
drain elbows, 400mm pipe
section and flue clamp.
Part No = 5136153
Part No = 5136164
45° e lbow and
flue clamp.
Part No = 5136150
Part No = 5136161
87° elbow and
flue clamp.
Part No = 5136151
Part No = 5136162
87° elbow and
flue clamp.
Part No = 5136151
Part No = 5136162
500mm extension piece
complete with clamp and
wall support bracket.
Part No = 5136149
Part No = 5136160
Flue support
bracket.
Part No = 5136152
Part No = 5136163
F
lue support
bracket.
Part No = 5136152
Part No = 5136163
Flue joint l ocking
band
Part No = 5136154
Part No = 5136165
Horizontal balanced flue kit
complete with 87 °elbow, wall
plate and terminal section.
Part No = 5136146
Part No = 5136157
To condensate
d
rain or
treatment
tank. 32mmØ
outlet
Paramount two
30kW - 115kW
Sirius WH
50kW - 110kW
Side view
A
Boiler Type Boiler Size Maximum total Maximum number Flue size
flue length of 87° bends InletØ OutletØ
Sirius WH 50 70 kW 9m 4 80 125mmØ
Sirius WH 90 –110 kW 9m 4 100 150mmØ
Paramount Two 30 40 kW 10m 2 80 125mmØ
Paramount Two 60 110 kW 5m 2 100 150mmØ
Each 87° bend reduces the total flue length by 1000mm. Each 45° bend reduces the total flue length by 500mm.
All horizontal flues should be installed ensuring there is a rise along its length.
Each condensate drain reduces the total flue length by 1000mm.
The part numbers for the Sirius WH
50 70kW and the Paramount two
3
0 40kW are shown in red.
The part numbers for the Sirius WH
90 110kW and the Paramount two
60 115kW are shown in blue.
All components come with a joint
locking band, although additional
bands are available using the part
numbers below.
All flue lengths and terminal pieces
include a flue support bracket.
Additional brackets are available using
the part numbers below.
The horizontal terminal section comes
complete with a wall tidy plate.
For Sirius WH boilers from 90 110kW
and the Paramount two 60 115kW
b
oilers require an adaptor to be fitted
directly on to the boiler before using
the flue components below. This
adaptor is included in each horizontal
flue terminal kit.