Ecoskid Data Tables
18 ECOSKID
Paramount and Baxi Ecogen CHP
MODEL NUMBER Unit
ECO-P56E ECO-P66E ECO-P86E ECO-P106E ECO-P121E ECO-P141E
Boiler 1 Size (Max Output) kW 30 40 60 80 95 115
Mini-CHP Size (Max Output) kW 26 26 26 26 26 26
Total Output (Min/Max) kW 56 66 86 106 121 141
Gas Consumption @ Max Output Nat Gas M³/Hr 5.66 6.46 8.46 10.46 12.56 14.66
Gas Consumption @ Max Output LPG M³/Hr 2.18 2.49 3.26 4.03 4.83 5.64
Nominal Inlet Gas Pressure (Nat Gas/LPG) mbar 19 23 / 35 39
Available External Pump (Head Flow Rate @ 20°C) kPa 101.15 kPa 101.15 kPa 101.15 kPa 98.59 kPa 97.41 kPa 99.09 kPa
Ltr/sec @ 0.67 @ 0.79 @1.03 @1.27 @1.45 @1.69
Electrical Supply Voltage V / Hz 230/50 230/50 230/50 230/50 230/50 230/50
Power Consumption @ Max Flow (Start/Run) A 7.94 / -0.9 7.96 / -0.88 8.00 / -0.84 8.15 / -0.69 8.44 / -0.4 8.85 / -0.01
External Flue Size (Boilers/Baxi Ecogen CHP) mm 80/125 80/125 110/160 110/160 110/160 110/160
60/100 60/100 60/100 60/100 60/100 60/100
Hydraulic Operating Pressure (Min/Max) Bar 1bar 3bar 1bar 3bar 1bar 3bar 1bar 3bar 1bar 3bar 1bar 3bar
Maximum Flow Temperature °C 80 80 80 80 80 80
Skid Weight (Empty) kg 486 486 494 505 517 517
2 x Paramount Boilers
MODEL NUMBER Unit ECO-P60 ECO-P80 ECO-P120 ECO-P160 ECO-P190 ECO-P230
Number of Boilers 2 x 30kW 2 x 40kW 2 x 60kW 2 x 80kW 2 x 95kW 2 x 115kW
Total Output (Min/Max) kW 60 80 120 160 190 230
Gas Consumption @ Max Output Nat Gas M³/Hr 6.4 8 12 16 20.2 24.4
Gas Consumption @ Max Output LPG M³/Hr 2.46 3.08 4.62 6.15 7.77 9.38
Nominal Inlet Gas Pressure (Nat Gas/LPG) mbar 19 - / 35 39
Available External Pump (Head Flow Rate @ 20°C) kPa 108.72 kPa 103.81 kPa 109.94 kPa 109.14 kPa 104.31 kPa 98.16 kPa
Ltr/sec @ 0.72 @ 0.96 @ 1.44 @ 1.91 @ 2.27 @ 2.75
Electrical Supply Voltage V 230/50 230/50 230/50 230/50 230/50 230/50
Power Consumption @ Max Flow (Start/Run) A 3.68 / 3.44 3.72 / 3.46 3.80 / 3.49 4.10 / 3.65 4.68 / 3.94 5.5 / 4.35
External Flue Size mm 80 / 125 80 / 125 110 / 160 110 / 160 110 / 160 110 / 160
Hydraulic Operating Pressure (Min/Max) Bar 1bar 3bar 1bar 3bar 1bar 4bar 1bar 4bar 1bar 4bar 1bar 4bar
Maximum Flow Temperature °C 85 85 85 85 85 85
Skid Weight (Empty) kg 424 424 440 462 486 486