Baxi EcoBlue Advance Heat Quick Start Manual Page 27

  • Download
  • Add to my manuals
  • Print
  • Page
    / 64
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 26
7212290 - 02 (08/14) EcoBlue Advance Heat 27
Before Installation 5
5.3.5 Condensate Drain
FAILURE TO INSTALL THE CONDENSATE
DISCHARGE PIPEWORK CORRECTLY WILL AFFECT
THE RELIABLE OPERATION OF THE BOILER.
CAREFUL CONSIDERATION MUST BE GIVEN TO
THE POSSIBILITY OF THE PIPEWORK BEING
SUBJECT TO FREEZING CONDITIONS AND
APPROPRIATE MEASURES TAKEN TO PREVENT
BLOCKAGE. CORRECT INSTALLATION IN
ACCORDANCE WITH THIS SECTION WILL
CONSIDERABLY MINIMISE THE LIKELIHOOD OF
BLOCKAGE AND SUBSEQUENT BOILER LOCK-OUT.
A CONDENSATE DISCHARGE PUMP AND PIPE
‘TRACE HEATING’ ARE AVAILABLE AS
ACCESSORIES - see paragraphs 5.3.5.12 to 5.3.5.15
for further details.
The condensate discharge pipe MUST NOT RISE at
any point along its length. There MUST be a fall of AT
LEAST 2.5° (50mm per metre) along the entire run
EXCEPT when employing a suitable condensate pump
in basement and cellar or similar applications.
The boiler condensate trap incorporates a water seal of
75mm, therefore it is unnecessary to install an
additional air break and trap in the discharge pipework.
1. The condensate outlet will accept 21.5mm (
3
/
4
in) plastic
overflow pipe. It is strongly recommended that this
discharges internally into the household drainage system.
Where this is not possible, discharge into an outside drain is
permissible providing every possible precaution is taken to
prevent freezing.
2. Ensure the discharge of condensate complies with any
national or local regulations in force. BS 6798 & Part H1 of the
Building Regulations give further detailed guidance.
3. The discharge pipe should be run in a proprietary drain pipe
material e.g. PVC, PVC-U, ABS, PVC-C or PP.
4. Metal pipework is NOT suitable for use in condensate
discharge systems.
5. The pipe should be a minimum of 21.5mm diameter and must
be supported using suitably spaced clips of the correct design to
prevent sagging.
6. It is advisable that the full length of condensate pipe is
run internally and preferably be less than 3 metres.
7. Internal runs greater than 3 metres or runs in cold areas
should use 32mm waste pipe.
8. External runs MUST be a MINIMUM of 32mm and fully
insulated with material suitable for external use.
Examples are shown of the following methods of
termination:-
i) to an internal soil & vent pipe
ii) via an internal discharge branch (e.g. sink waste)
downstream of the trap
iii) to a drain or gully
iv) to a purpose made soakaway
v) pumped into an internal discharge branch (e.g.
sink waste) downstream of the trap
vi) pumped into an external soil & vent pipe
vii) to a drain or gully with extended external run &
trace heating
It is strongly recommended to discharge
internally into the household drainage system. If
connecting to a rain water drain, that drain MUST
discharge into a foul drain.
21.5mm
32mm
Insulation
2.5° Minimum fall
i) Termination to an internal soil
and vent pipe
450mm min*
50mm per metre of pipe run
*450mm is applicable to properties up
to 3 storeys.
For multi-storey building installations
consult BS 6798.
Boiler
2.5° Minimum fall
ii) External termination via
internal discharge branch
e.g sink waste - downstream*
Sink
Pipe must terminate
above water level but
below surrounding
surface. Cut end at 45°
50mm per metre
of pipe run
*It is NOT RECOMMENDED to connect upstream
of the sink or other waste water receptacle !
Page view 26
1 2 ... 22 23 24 25 26 27 28 29 30 31 32 ... 63 64

Comments to this Manuals

No comments