EcoBlue Advance HeatInstallation and Service ManualGas Fired Wall Mounted Powered Flue Condensing Boiler13 - 16 - 19 - 25 - 30enUnited KingdomThese in
10 EcoBlue Advance Heat1 Introduction7212290 - 02 (08/14)1.5.2 Installer's ResponsibilityThe installer is responsible for the installatio
7212290 - 02 (08/14) EcoBlue Advance Heat 11Introduction 11.6.3 StandardsCodes of Practice - refer to the most recent versionIn GB the followi
12 EcoBlue Advance Heat2 Safety7212290 - 02 (08/14)2 Safety2.1 General Safety Instructions2.2 RecommendationsDANGER If you smell gas: 1. Turn off t
7212290 - 02 (08/14) EcoBlue Advance Heat 13Safety 22.3 Specific Safety Instructions2.3.1 HandlingGeneral• The following advice should be a
14 EcoBlue Advance Heat3 Technical Specifications7212290 - 02 (08/14)3 Technical Specifications3.1 Technical DataNOTE: All data in this section are no
7212290 - 02 (08/14) EcoBlue Advance Heat 15Technical Specifications 33.2 Dimensions and ConnectionsIMPORTANT: The 1.5° fall provided by the elbow ist
16 EcoBlue Advance Heat3 Technical Specifications7212290 - 02 (08/14)3.3 Electrical DiagramGas ValveSafetyThermostatReturnSensorFlowSensorParameterUni
7212290 - 02 (08/14) EcoBlue Advance Heat 17Description of the Product 44 Description of the Product4.1 General Description1. The Baxi EcoBlue Advance
18 EcoBlue Advance Heat 7212290 - 02 (08/14)4 Description of the Product4.2 Operating Principle1. Switched Live On: When the boiler switched live turn
7212290 - 02 (08/14) EcoBlue Advance Heat 19Description of the Product 44.3 Main Components1. Heat Exchanger2. Combustion Control
2 EcoBlue Advance Heat 7212290 - 02 (08/14)You have just purchased one of our appliances and we thank you for the trust you have placed in our product
20 EcoBlue Advance Heat 7212290 - 02 (08/14)4 Description of the Product4.4 Control Panel Description4.4.1 User Interaction Controller
7212290 - 02 (08/14) EcoBlue Advance Heat21Description of the Product 44.5 Standard Delivery1. The pack contains: Boiler Wall
22 EcoBlue Advance Heat 7212290 - 02 (08/14)5 Before Installation5 Before Installation5.1 Installation RegulationsInstallation must be carried out in
7212290 - 02 (08/14) EcoBlue Advance Heat 23Before Installation 55.2.2 Electrical Supply1. External wiring must be correctly earthed, polarise
24 EcoBlue Advance Heat 7212290 - 02 (08/14)5 Before Installation5.2.7 System Details - GeneralWater Circulating Systems1. The appliance is su
7212290 - 02 (08/14) EcoBlue Advance Heat 25Before Installation 55.2.9 Sealed Systems Details1. SAFETY VALVE - A safety valve complying with t
26 EcoBlue Advance Heat 7212290 - 02 (08/14)5 Before Installation5.3 Choice of the Location5.3.1 Location of the Appliance Due to t
7212290 - 02 (08/14) EcoBlue Advance Heat 27Before Installation 55.3.5 Condensate Drain FAILURE TO INSTALL THE CONDENSATE
28 EcoBlue Advance Heat 7212290 - 02 (08/14)5 Before Installation9. If the boiler is fitted in an unheated location the entirecondensate discharge pip
7212290 - 02 (08/14) EcoBlue Advance Heat 29Before Installation 55.3.6 Clearances - Access in Service1. A flat vertical area is required for t
7212290 - 02 (08/14) EcoBlue Advance Heat 3Installer Notification GuidelinesChoose BuildingRegulations NotificationRouteContact your relevant LocalAut
30 EcoBlue Advance Heat 7212290 - 02 (08/14)5 Before Installation5.3.7 Flue/Chimney Location1. The following guidelines indicate the general r
7212290 - 02 (08/14) EcoBlue Advance Heat 31Before Installation 5 Due to the nature of the boiler a plume of water vapour will
32 EcoBlue Advance Heat 7212290 - 02 (08/14)5 Before Installation5.3.8 Horizontal Flue/Chimney Systems1. The standard telescopic flue is suita
7212290 - 02 (08/14) EcoBlue Advance Heat 33Before Installation 55.3.9 Flue/Chimney Trim1. The flexible flue trims supplied can be fitted on t
34 EcoBlue Advance Heat 7212290 - 02 (08/14)5 Before Installation5.4 Unpacking & Initial Preparation5.4.1 Unpacking 1. Follow the procedure on
7212290 - 02 (08/14) EcoBlue Advance Heat 35Before Installation 55.4.4 Filling the Condensate Trap 1. The condensate trap must be filled with wa
36 EcoBlue Advance Heat 7212290 - 02 (08/14)6 Installation6 Installation6.1 Air Supply / Flue Gas Connections6.1.1 Connecting the Top Flue HORIZ
7212290 - 02 (08/14) EcoBlue Advance Heat 37Installation 610. Remove the boiler blank adaptor and replace with the boileradaptor ensuring that the ga
38 EcoBlue Advance Heat 7212290 - 02 (08/14)6 Installation6.1.2 Connecting the ‘In Case’ Rear Flue Internal Fitting Kit part no. 72
7212290 - 02 (08/14) EcoBlue Advance Heat 39Installation 69. Undo the screws securing the rear flue blanking plate. Firmlygrip the central spigot and
4 EcoBlue Advance HeatContentsContents1 Introduction1.1 General1.2 Additional Documentation1.3 Symbols Used1.4 Abbreviations1.5 Extent of Liabilities1
40 EcoBlue Advance Heat 7212290 - 02 (08/14)6 Installation6.2 Electrical ConnectionsY PlanDiverterValveCylinderStatRoomStatBoilerPumpTimer230V50HzL NE
7212290 - 02 (08/14) EcoBlue Advance Heat 41Installation 66.3 Filling the System See Section 5.2.6. for details of treating the system,Section 5.
42 EcoBlue Advance Heat 7212290 - 02 (08/14)7 Commissioning7 Commissioning7.1 General1. Reference should be made to BS:EN 12828 & 14336 whencommis
7212290 - 02 (08/14) EcoBlue Advance Heat 43Commissioning 77.4 Gas Settings7.4.1 ‘Chimney Sweep’ Mode (CSM)1. The current operating condition of
44 EcoBlue Advance Heat 7212290 - 02 (08/14)7 CommissioningSet Boiler to Maximum RateAllow the combustion to stabilise. Do not insert probeto avoid ‘f
7212290 - 02 (08/14) EcoBlue Advance Heat 45Commissioning 77.5.1 Check the Operational (Working) Gas Inlet Pressure 1. Ensure
46 EcoBlue Advance Heat 7212290 - 02 (08/14)7 Commissioning7.6 Final Instructions1. Carefully read and complete all sections of the BenchmarkCommissio
7212290 - 02 (08/14) EcoBlue Advance Heat 47Operation 88 Operation8.1 General1. It is the responsibility of the installer to instruct the user in thed
48 EcoBlue Advance Heat 7212290 - 02 (08/14)8 Operation8.4 Use of the Control Panel8.5 Frost Protection1. To prevent radiators and pipework from freez
7212290 - 02 (08/14) EcoBlue Advance Heat 49Settings 99 Settings9.1 Parameters The operating parameters for this boiler are factory set.
7212290 - 02 (08/14) EcoBlue Advance Heat 5Contents5.3.9 Flue/Chimney Trim5.3.10 Terminal Guard5.3.11 Flue/Chimney Deflector5.3.12 Flue/Chimney Access
50 EcoBlue Advance Heat 7212290 - 02 (08/14)10 Maintenance10 Maintenance10.1 GeneralPlugAnalyser ProbeFlue SamplingPointAir SamplingPointWARNINGWhen c
WARNING Ensure that the boiler is cool. Ensure that both the gas and electrical supplies to
52 EcoBlue Advance Heat 7212290 - 02 (08/14)10 Maintenance10.3 Specific Maintenance OperationWARNINGWhen changing components ensure that both thegas a
7212290 - 02 (08/14) EcoBlue Advance Heat 53Maintenance 10 Removal of the fan air duct and flue outlet duct is necessary to e
54 EcoBlue Advance Heat 7212290 - 02 (08/14)10 Maintenance10.3.6 Flow Temperature Sensor (Fig. 51) The sensor is fitted in a ‘dry’ poc
7212290 - 02 (08/14) EcoBlue Advance Heat 55Maintenance 10View frombehindCombustionControl UnitGas ValveSecuring ScrewsCombustionControl Unit10.3.10
56 EcoBlue Advance Heat 7212290 - 02 (08/14)10 MaintenanceBurner ManifoldControl & FanAssemblyLower PanelUser Interaction ControllerRotaryKnob10.3
7212290 - 02 (08/14) EcoBlue Advance Heat 57Maintenance 1010.3.13 Setting the Gas Valve (CO2Check) The CO2must be only be checked and a
58 EcoBlue Advance Heat 7212290 - 02 (08/14)11 Troubleshooting11 Troubleshooting11.1 Error CodesStatus signalDescription Remedial actions by serviceen
7212290 - 02 (08/14) EcoBlue Advance Heat 59Troubleshooting 11Remedial actions by serviceengineer Status signalDescription Possible cause s1 flashred
6 EcoBlue Advance HeatContents10 Maintenance10.1 General10.2 Standard Inspection & Maintenance Operation10.3 Specific Maintenance Operation10.3.1
60 EcoBlue Advance Heat 7212290 - 02 (08/14)12 Decommissioning12 Decommissioning12.1 Decommissioning Procedure1. Disconnect the gas & electric sup
7212290 - 02 (08/14) EcoBlue Advance Heat 61Spare Parts 1313 Spare Parts13.1 General1. If, following the annual inspection or maintenance any part oft
*All installations in England and Wales must be to Local Authority Building Control (LABC) either directly or through aCompetent Persons Scheme. A Bui
www.centralheating.co.ukIt is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed
BAXI A Trading Division of Baxi Heating UK Ltd (3879156)Brooks House, Coventry Road, Warwick. CV34 4LLAfter Sales Service 0844 871 1525 Technical Enqu
7212290 - 02 (08/14) EcoBlue Advance Heat 7Introduction1 Introduction1.1 General WARNING Installation, repair and main
8 EcoBlue Advance Heat1 Introduction7212290 - 02 (08/14)1.3 Symbols Used DHW: Domestic hot water CH: Central heating GB: Great Britain
7212290 - 02 (08/14) EcoBlue Advance Heat 9Introduction 11.5 Extent of Liabilities1.5.1 Manufacturer's Liability Our products are manufactu